What the Code Actually Says · Episode 09

The Shared Neutral

Two hot conductors, one shared neutral.
NEC 210.4
▶ Watch the episode All episodes

The bottom line

A multiwire branch circuit uses two hot conductors and one shared neutral. Put the two hots on opposite legs. The neutral then carries only the difference between the two loads. Put both hots on the same leg, and the neutral carries the sum. That overloads the neutral. Give the circuit a common disconnect. Pigtail the neutral. Do not run the neutral through a device.

Code sections

NEC 210.4(A)

A multiwire branch circuit has two or more hot conductors with a voltage between them, and one grounded (neutral) conductor. The neutral has an equal voltage to each hot conductor.

NEC 210.4(B)

Install a means to disconnect all hot conductors at the same time. Use a 2-pole breaker or a listed handle tie. Both hots share a neutral, so both can be live.

NEC 210.4(C)/(D)

Group the conductors of each multiwire circuit. Identify them at the panel.

NEC 300.13(B)

Pigtail the shared neutral. The neutral must not depend on a device to stay connected. If you remove one receptacle, the neutral must stay connected for the devices downstream.