What the Code Actually Says · Episode 16

Solar on the Busbar: the 120% Rule

How much solar a busbar can take, and the two numbers that set it.
NEC 705.12
▶ Watch the episode Read the article All episodes

The bottom line

Under the 120% rule, 125% of the inverter output circuit current plus the rating of the breaker protecting the busbar must not exceed 120% of the busbar rating, with the sources at opposite ends of a busbar that contains loads. A 200 A busbar with a 200 A main leaves 40 A (an inverter up to 32 A). The same main on a 225 A busbar leaves 70 A. A 175 A main on the 200 A busbar leaves 65 A, if the Article 220 load calculation still supports the smaller main.

The handbook table (Exhibit 705.2) and the math

MainBusbar120% of busbarLeft for the source (125% of output)Inverter up to
100 A100 A120 A20 A16 A
100 A125 A150 A50 A40 A
200 A200 A240 A40 A32 A
200 A225 A270 A70 A56 A

The first four columns are the handbook table, Exhibit 705.2; the last column is 125% backed out. Your jurisdiction may enforce a different Code year; check which version applies.

What the Code actually says

705.12(A)(1)

The feeder ampacity is greater than or equal to 125 percent of the power-source output circuit current.

705.12(B)(1)

The sum of 125 percent of the power source(s) output circuit current and the rating of the overcurrent device protecting the busbar shall not exceed the busbar ampere rating.

705.12(B)(2)

Where two sources, one a primary power source and the other another power source, are located at opposite ends of a busbar that contains loads, the sum of 125 percent of the power-source(s) output circuit current and the rating of the overcurrent device protecting the busbar shall not exceed 120 percent of the busbar ampere rating. The busbar shall be sized for the loads connected in accordance with Article 220.

705.12(B)(3)

The sum of the ampere ratings of all overcurrent devices on panelboards, both load and supply devices, excluding the rating of the overcurrent device protecting the busbar, shall not exceed the ampacity of the busbar. The rating of the overcurrent device protecting the busbar shall not exceed the rating of the busbar.

705.12(B)(2) label

WARNING: POWER SOURCE OUTPUT. DO NOT RELOCATE THIS OVERCURRENT DEVICE.

A (B)(3) example

A 125 A panelboard feeding only a few circuits: two 40 A solar breakers and one 30 A load breaker add to 110 A, under the 125 A busbar, so it complies. The breaker protecting the busbar must not be rated above 125 A. The rule does not say where on the bus the breakers sit.

What the handbook adds (commentary, not Code)

The required ampacity is based on the inverter output circuit current, rather than on the overcurrent device inside the inverter. Unlike service equipment, 705.12(B)(3) caps the total rating of the breakers on a panelboard.

Go further

The field guide: Solar on the Busbar, every 705.12 method worked through with field numbers.

Check your plans: a quick $195 written review of one single-line diagram for a load-side PV connection, before you submit.

Tools & parts

The panel label, the inverter data sheet (output circuit current), and the Code book. Any hand tool = Klein Tools.

On the bench

Solar on the Busbar (paperback) · Solar on the Busbar (Kindle) · DYMO Rhino label tape (warning labels) · NEC 2023 Handbook (NFPA) · NEC 2023 code book · NEC 2026 Handbook (NFPA) · NEC 2026 code book · Ugly's Electrical References, 2023 · Klein 32500 11-in-1 screwdriver · Klein 9230 30 ft tape · WAGO 221 lever-nut kit

As an Amazon Associate I earn from qualifying purchases.